Truma BG 10 BGE 10

Official technical documentation and workshop diagnostics for Boiler BG 10 / BGE 10.

View official manual on manufacturer's site ↗

Technical Specifications

Operating Voltage12V DC / 230V AC
Power Consumption12V: Ignition 0.16A, Heating 0.12A, Standby 0.05A; 230V: 850W (3.7A) / 1300W (5.7A)
Gas Or PressureLiquid gas (propane / butane) at 30 mbar
Fuse Ratings1.6A slow-acting fine wire fuse (EN 60127-2-3)
Dimensions CutoutCowl cutout: see technical drawings, max pump pressure 2.8 bar, system pressure max 4.5 bar

Master Troubleshooting & Diagnostics Matrix

Error Code / IndicatorSymptom / MeaningPossible CauseStep-by-Step DIY FixSuggested Actions
N/A
The boiler won't run once switched on (gas mode)
No 12V power supply
Check the battery voltage is at least 10.5V, and check the electronic control unit's fine-wire fuse. Contact an authorised service agent if this doesn't resolve it.
DIY Check / Tech Fallback
N/A
The boiler won't run once switched on (gas mode)
Window open above cowl
Close the window above the cowl.
DIY Safe
N/A
The boiler switches on but doesn't run, and the red LED comes on after roughly 30 seconds
Cowl cover is fitted
Take the cowl cover off and clear away any dirt or debris found there.
DIY Safe
N/A
The boiler switches on but doesn't run, and the red LED comes on after roughly 30 seconds
No gas supply or incorrect gas pressure
Check gas valves and gas cylinder.
DIY Safe
N/A
The boiler switches on but doesn't run, and the red LED comes on after roughly 30 seconds
Air in gas supply
Switch the appliance off, leave it for 5 minutes to bleed off any trapped air, then switch it back on to clear the fault.
DIY Safe
N/A
After a long spell of running, the boiler faults out and the red LED comes on
Overtemperature sensor has activated
Close the drain valve and top up the water content if it's low. Switch the appliance off for 5 minutes and back on to clear the fault; if it recurs, contact an authorised service agent.
DIY Check / Tech Fallback
N/A
The boiler won't run once switched on (BGE 10 electrical mode)
No 230V power supply
Hook the vehicle up to a mains supply and/or check the residual current protective device.
DIY Safe
N/A
The boiler won't run once switched on (BGE 10 electrical mode)
Overtemperature sensor has activated
Close the drain valve and top up the water content if it's low. The electric heating element has its own overtemperature sensor - turn it off at the control panel, wait 10 minutes and turn it on again. Contact an authorised service agent if the problem persists.
DIY Check / Tech Fallback
N/A
Heats up too slowly with the switch set to 850W (BGE 10 electrical mode)
Insufficient heating output selected for conditions
Contact Truma Service or an authorized workshop.
Professional Intervention Required
N/A
Water dripping from drain valve
Water pressure too high
Check the water pressure doesn't exceed 2.8 bar - fit a pressure reducer if connecting to a mains water supply.
DIY Safe
N/A
Warm water comes out of the cold tap
Hot water is flowing back into the cold supply.
Fit a non-return valve into the cold water supply, following the installation instructions.
DIY Safe