Technical Specifications

Operating Voltage12V DC / 24V DC
Power Consumption61W
Fuse Ratings15A (at 12V) / 7.5A (at 24V)
Dimensions CutoutRefer to fig. s, side 10

Master Troubleshooting & Diagnostics Matrix

Error Code / IndicatorSymptom / MeaningPossible CauseStep-by-Step DIY FixSuggested Actions
UKL = 0 V
Compressor does not run due to break in supply line between battery and electronics.
Open circuit in the connection cable, defective main switch, or blown inline fuse.
Restore the connection. Replace the main switch if it is defective. Replace the fuse if an extra fuse has tripped.
DIY Safe
UKL <= UTIL
Compressor does not run because battery voltage is too low.
Battery discharged, loose cable connection, poor corrosion connection, insufficient battery capacity, or inadequate cable cross-section.
Charge the battery, clean or tighten connections, and replace undersized cables.
DIY Safe
UKL >= UTIL
Compressor does not run due to high ambient temperature or poor ventilation.
Ambient temperature is too high, ventilation is insufficient, condenser is dirty, or fan is defective.
Improve ventilation, clean the condenser, and replace the defective fan.
DIY Safe
N/A
Compressor runs constantly and inside temperature is too cold on control setting 1.
Thermostat sensor is not connected to the evaporator, or there is a short circuit in the thermostat wiring.
Fasten the thermostat sensor or replace the thermostat.
DIY Check / Tech Fallback
N/A
Cooling capacity is reduced and inside temperature rises.
Frost buildup on the evaporator, ambient temperature too high, poor ventilation, dirty condenser, or depleted battery capacity.
Defrost the evaporator, clean the condenser, improve ventilation, and charge the battery.
DIY Safe
N/A
Water inside or under the refrigerator.
Water drain channel is blocked, or stored food is obstructing the water flow to the collector.
Clear the water drain with the cleaning tool kept in the drain opening, and move food so none of it touches the back wall.
DIY Safe
N/A
Unusual noises such as loud humming.
Part of the cooling circuit is touching the wall so it can't vibrate freely, or something has got wedged behind the cooling unit.
Carefully bend the component away from the wall or remove the foreign object.
DIY Safe