Alde Compact 3020 PS
Official technical documentation and workshop diagnostics for Compact 3020 PS.
Technical Specifications
Master Troubleshooting & Diagnostics Matrix
| Error Code / Indicator | Symptom / Meaning | Possible Cause | Step-by-Step DIY Fix | Suggested Actions |
|---|---|---|---|---|
Gas failure | The boiler won't fire up on gas. | Empty LPG bottle, closed main valve, unsuitable gas type for temperature, blown 12V fuse, low supply voltage below 11V, blocked or damaged exhaust hose, obstructed flue, incorrect gas pressure, or untripped/tripped crash sensor. | Check gas supply, open main valve, use propane for cold temperatures, inspect 12V fuse and supply voltage, ensure exhaust hose and flue are clear, verify gas pressure using the hob burners, and restart the boiler. If the fault persists, contact an authorised service agent. | DIY Check / Tech Fallback |
Connector failure | Communication error between boiler and panel. | Either the red cable (or its contacts) between boiler and panel has a fault, or something wired into the boiler's black contact - an AC unit or iNet box, say - has come loose. | Check the red connection cable and terminals between the boiler and panel, and inspect auxiliary cables connected to the black contact. If the issue remains unresolved, contact an authorised service agent. | DIY Check / Tech Fallback |
Heater not found | Connection error between boiler and control panel. | Problem with boiler printed circuit board or incompatible software versions. | Verify board compatibility (article number 3020 145 required). If the issue remains unresolved, contact an authorised service agent. | DIY Check / Tech Fallback |
Overheat glycol | Glycol temperature has overheated, often due to high power combined with air pockets. | Air pockets in the system, low glycol level in expansion vessel (below min mark when cold), broken circulation pump, or disconnected pump. | Bleed the heating system thoroughly, ensure fluid level is at least 1 cm above the min mark, and check circulation pump operation. Allow glycol temperature to drop below 50 °C, then disconnect and reconnect the 12V supply. | DIY Safe |
Overheat lockout | Boiler locked out due to prior over-temperature condition. | Temperature inside the boiler exceeded safe limits. | Disconnect and reconnect the 12V supply to the boiler once the temperature has dropped. | DIY Safe |
Overheat PCB | Overheating detected in the boiler unit or compartment. | Excessive ambient temperature or restricted airflow around the PCB. | Allow the boiler to cool down, then disconnect and reconnect the 12V supply. If the fault persists, contact an authorised service agent. | DIY Check / Tech Fallback |
Heater failure | Boiler operation halted due to hardware fault. | Damaged printed circuit board. | Disconnect and reconnect the 12V supply to the boiler. If the fault persists, contact an authorised service agent. | DIY Check / Tech Fallback |
Low battery voltage | Boiler stops operating due to insufficient supply voltage. | Vehicle battery voltage dropped below 10.8V. | Ensure the vehicle charging system provides proper voltage; the system will reset automatically when voltage reaches 11V. | DIY Safe |
Fan failure | Combustion fan fails to operate correctly. | Defective combustion fan or motor. | Contact an authorised service agent. | Professional Intervention Required |
Window open | Gas operation stops while electric operation continues. | A window switch indicates an open window near the wall flue. | Close the window near the wall flue to resume gas operation. | DIY Safe |
Panel failure | Control panel malfunctions. | Panel exposed to high humidity over an extended period. | Allow the panel to dry out completely and restart it. If the fault persists, contact an authorised service agent. | DIY Check / Tech Fallback |
Opt. dongle not found | Optional option card missing. | Previously identified option card has been disconnected or removed. | Reconnection required or uninstall accessories requiring the card. Cut 12V power, connect the card, and restore 12V power. If the fault persists, contact an authorised service agent. | DIY Check / Tech Fallback |
Load monitor not found | Load monitor missing or unresponsive. | Load monitor unplugged or defective. | Confirm the load monitor's properly wired in. Contact an authorised service agent if the fault's still there. | DIY Check / Tech Fallback |
Zone 1 sensor error / Zone 2 sensor error | Room temperature regulation fails for a specific zone. | Room sensor unplugged or defective sensor/cable. | Check that the sensor is plugged in and inspect the wiring. If the fault persists, contact an authorised service agent. | DIY Check / Tech Fallback |
Hot water sensor error | Hot water monitoring fails, though passive heating may still occur. | Hot water sensor unplugged or defective. | Check sensor connection. If the fault persists, contact an authorised service agent. | DIY Check / Tech Fallback |
Outdoor sensor error | Outdoor temperature display or control missing. | Outdoor temperature sensor unplugged or defective. | If it's been deliberately disconnected, press "dismiss" on the control panel. | DIY Safe |
CI-bus error | Communication failure on the yellow control panel connector. | High communication load or damaged wiring/connections to the vehicle master panel. | Check the cable, connections, and vehicle master panel. If the fault persists, contact an authorised service agent. | DIY Check / Tech Fallback |
iNet Connection error | Remote app integration lost. | iNet-box unplugged or defective. | If it's been deliberately disconnected, press "dismiss" on the control panel. | DIY Safe |
Remote Control error | External remote control unresponsive. | Remote control connected to JP3 on panel back is unplugged or defective. | Check cable and connections, or press "uninstall" on the control panel if intentionally removed. | DIY Safe |
Alde Voice not found | Voice control unit unresponsive. | Alde Voice Control main unit unplugged or defective. | If it's been deliberately disconnected, press "dismiss" on the control panel. | DIY Safe |
N/A | "No match Heater/Panel" message displayed | The control panel is incompatible with the boiler's PCB. | Check the control panel part number - control panel 3020-013 is for the 3020 A-series boiler, 3020-113 is for the 3020 HE-series boiler. | DIY Safe |
N/A | The system is completely dead / the control panel is blank | Blown fuse, insufficient 12V supply, or a loose cable connection. | Check the 20mm T3.15 amp glass fuse in the boiler (under the lid of the black plastic service hatch, in a green plastic fuse holder). Check the 12V supply to the boiler is above 12V. Check the 12V cable is plugged into both the boiler and the Alde control panel. | DIY Safe |
N/A | The boiler will not ignite on gas | Gas cylinder empty or not propane, or the boiler genuinely doesn't need gas at this time. | Check the gas cylinder is full and try a different gas cylinder, ensuring it is propane gas. Note: the system may not need to use gas heating if also using electric heating, and the boiler will not ignite if the fluids are already at operating temperature - neither of these is a fault. | DIY Safe |
N/A | The boiler will not heat on 230V electric | A 230V isolator switch is off, no 230V supply, or the fluids are already at operating temperature. | Check that any 230V isolator switches are on (they often have an LED indicator). Check the 230V supply to the vehicle. Note: the boiler will not heat further if the fluids are already at operating temperature - this is not a fault. | DIY Safe |
N/A | No hot water | 'Hot water ignore' or 'constant pumping' is activated on the Alde control panel, a conflicting setting is active, or a freshwater supply/pump issue. | Check that 'hot water ignore' and 'constant pumping' are not activated on the Alde control panel, check for other conflicting settings, and check the freshwater supply and water pump. | DIY Safe |
N/A | No central heating | Air in the system, low heat transfer fluid, circulation pump not responding, 'hot water boost' activated, obstructed vents, or degraded heat transfer fluid. | Bleed any air out of the system. Check the expansion tank's fluid level and the condition of the heat transfer fluid, and confirm the circulation pump's actually responding. Make sure "hot water boost" isn't switched on at the Alde control panel, try running gas and electric heating together, and check nothing's blocking the vents in the furniture. | DIY Safe |
N/A | "Panel failure 1" or "Panel failure 2" message displayed | Moisture is trapped in the control panel. | Remove the Alde control panel from the vehicle and air it in a warm, dry place overnight. | DIY Safe |
N/A | "Overheat red fail" or "Overheat blue fail" message displayed | Air in the system, low fluid level, or the circulation pump not responding. | Bleed any air out of the system, and check the expansion tank's fluid sits at least 1cm above the min mark once cool. Confirm the circulation pump's responding, then give the fluid 15 minutes to cool down. | DIY Safe |
N/A | "Overheat PCB" message displayed | The boiler's failsafe has triggered, typically due to low fluid level or restricted ventilation. | Check the expansion tank's fluid sits at least 1cm above the min mark when cool, and confirm the boiler compartment is properly ventilated with nothing blocking the vents - don't store anything in there. | DIY Safe |
Frequently Asked Questions
Q: My hot water has only been lukewarm since a service - why?
The technician may have left the circulation pump in continuous mode, which is meant for testing and stops the hot water cylinder getting enough heat. Resetting the Alde control panel to its factory defaults is usually the simplest fix - see your heater's operating instructions.
Q: Why does my Alde heating gurgle since it was serviced?
The circulation pump may still be on speed 5, which technicians use to push air out of the system. Turn it back down to speed 2-3 for a touring caravan or a B- or C-class motorhome, or to just below speed 4 for an A-class. If the heating fluid was replaced, there may also be air trapped in the system - see your heater's operating instructions.
Q: Can I run the central heating in winter with the fresh water drained?
Yes - use it exactly as you normally would. The hot water cylinder has no heating elements that could burn out, so it does no harm.
Q: Which antifreeze products does Alde approve?
In the UK, the products meeting Alde Approval 40X0 2024 are: Comma Xstream G40; Fuchs Fricofin DP; Volkswagen Group G12evo; and Alde's own Protective Premium in G12++ and G12evo versions. (Alde stopped selling its G13 products at the end of 2023.) All come ready-mixed with deionised water, are magenta, can be mixed with each other, and give frost protection down to -37°C plus 5 years' corrosion protection - but always check the label. North America has its own, chemically different, approved list.
Q: What should I top up my Alde heating fluid with?
Ideally the same antifreeze that's already in it. Magenta fluid almost certainly means an Alde-approved antifreeze, so top up with any approved product - they can all be mixed. If the fluid isn't magenta, the safest option is to add just one or two cups of deionised water - you lose a little frost, corrosion and bacteria protection, but mixing incompatible antifreezes risks worse damage.
Then have the fluid replaced with an Alde-approved antifreeze as soon as you reasonably can.
Q: How can I run my Alde heating as efficiently as possible?
Turn on all the electric and gas/diesel heating you have available - this actually uses less energy overall. Set the thermostat to a comfortable temperature rather than turning it right up when you feel cold, or you'll overshoot and end up opening windows; a jumper and a setting a couple of degrees lower saves more. If you don't need hot water overnight, tell the system not to heat it then.
Each season, bleed any air out of the heating fluid, and keep the vents at the top and bottom of cupboards and lockers clear.
Q: How much current does Alde heating draw?
On 12V DC, how much it takes from the leisure battery varies a lot. It peaks at ignition - about 2 A for gas heating, about 20 A for diesel. For off-grid planning, allow roughly 1 A while gas heating is running and about 4 A for diesel; switched off, the standby drain is around 80 mA. On mains: UK mains is nominally 230V but usually nearer 240V in practice, so expect roughly 4.8 A at 1 kW, 9.5 A at 2 kW and 14.3 A at 3 kW.
Q: How long should it take to warm up my caravan or motorhome?
That depends on how the vehicle is built and insulated, how cold it is outside, and how much power you can give the heater - more power means more heat. Most manufacturers now aim for around an hour from cold to a comfortable temperature.
Q: Can I leave the Alde heating on low to protect against frost?
You can heat the vehicle through the winter, though if nobody's staying in it you may decide it isn't worth the running cost. On mains hook-up at home, for example, you could set 10°C with 2 kW of electric heating. Check inside regularly for condensation and signs of rodents, and bear in mind some lockers and compartments probably won't be protected from frost.
Q: What routine maintenance does an Alde system need?
The heating fluid needs replacing once its corrosion protection runs out - Alde-approved antifreezes (magenta) last 5 years. Bleeding air from the fluid now and then improves efficiency. Each season, check the boiler flue: the hose should be secure and undamaged, and the outlet free of blockages. After 10 or more days staying in the vehicle, top up the boiler's air cushion.
Before any frost, drain the fresh water - and while you do, make sure the red breather valve hasn't scaled up. See your heater's operating instructions for details. An annual service may be a legal requirement, particularly if the vehicle serves as an annex to a house, is hired out, or is somewhere people work.
Q: In summer, can I have hot water without the heating coming on?
Set the room temperature on the control panel to around 15°C. In summer that's low enough that the central heating will rarely circulate, day or night, while hot water is not affected.
Q: Which fluid is my Alde system filled with?
That's down to whoever installed it - ideally an Alde-approved antifreeze, which is magenta. Alde advises against any antifreeze it hasn't approved.
Q: Where should the fluid sit in the expansion tank?
With the system cold, about 1 cm higher than the Min mark. As the fluid heats up it expands towards the Max mark.
Q: How much fluid does the central heating hold?
Roughly 10-15 litres in a touring caravan or a B- or C-class motorhome, and 20-25 litres in an A-class motorhome or a boat.
Q: What does the air cushion reminder mean?
After 10 days' use, the Alde system prompts you to top up the air cushion in the hot water cylinder, which keeps it running smoothly. If there's been water in the system: turn off the water pump, open all the taps and the shower fully, open the safety drain valve for 5-10 seconds and then close it, and refill the water system as usual. If the system has been dry, you can ignore the reminder.
Q: Why does my hot water come out scalding?
By law, stored hot water has to be kept hot enough to scald, to stop legionella - a potentially deadly bacteria - from growing. The Alde TMV3, an aftermarket accessory, limits the temperature of the water reaching your taps and shower.
Q: How much hot water can an Alde system supply?
Expect roughly a 4-5 minute shower every half-hour. The aftermarket Alde TMV3 can cut down on hot water wasted in the shower, and the Alde Flow gives continuous hot water - it can be retrofitted to any Alde-equipped vehicle from the 2018 model year on, and in the UK is sold only through Moosewerks.
Q: Can I put any fresh water into my Alde system?
Only water that's pleasant to drink. Some sites in Spain, Portugal and North Africa supply water heavy in bleach or salt, which corrodes stainless steel. Even if a tap is labelled as drinking water, don't put it through the Alde system if you couldn't bear to drink it - unless your vehicle has a reverse-osmosis water filter of at least 4 stages.
Q: Which sterilising and descaling products are safe for my Alde system?
Anything the label says is safe for a stainless steel water cylinder. Clean Tabs make a range of suitable products that are easy to find.
Q: Do I need to drain the fresh water for winter?
Yes. A vehicle can be designed to winterise itself, but very few on sale are.
Q: Can gas/diesel and electric heating run together?
Yes, and Alde recommends it. You can also set the system to favour one source over the other - for example, whichever is cheaper.
Q: How much gas does Alde heating use?
As a rough guide, a 6 kg propane cylinder should last a weekend of gas heating - though in freezing weather it will go considerably faster.
Q: Is propane or butane the right gas for Alde heating?
Propane. Butane isn't suitable below 13°C (BS 5482 Part 1).
Q: Can I use Autogas?
Yes.
Q: Is it safe to run gas heating while driving?
Alde advises against it. A crash sensor on the bulkhead regulator doesn't change the main risk: drive onto a fuel forecourt with the gas heater running and fumes could be pulled straight into its combustion chamber - effectively the same as carrying a lit camping stove across the forecourt. You'd need to pull over and switch gas heating off before every fuel stop, and forgetting just once could be disastrous.
Q: I've filled up with B10 diesel abroad by mistake - is that a problem?
No need to worry - it does no harm in the short term, though B10 or stronger biodiesel shortens the burner's life if used long-term. Carry on using the diesel heating normally until you can top up with at least half a tank of a compatible fuel, and try not to repeat it.
Q: Which diesel fuels can I use?
Alde's diesel models - the Compact 4000 D and the 4000 D Plus - run on B7 diesel (EN 590) and XTL diesel (EN 15940). If you use agricultural or marine diesel, HVO meeting EN 15940 is also compatible.
Q: Is it OK to run diesel heating while driving?
Alde doesn't recommend it. It's technically possible, but if you forget to switch the diesel heating off before stopping to refuel it won't go down well with staff or other customers - and fumes could be drawn straight into the combustion chamber. An Alde engine heat exchanger is the better option for heat on the move.
Q: Can my Alde system be converted from gas to diesel?
It depends on how much the boiler compartment and diesel tank need reworking. The Compact 4000 D isn't a straight swap for a Compact 3030, for instance, and not every diesel tank has an accessible sender or a spare fuel pick-up. The cost may well rule it out - Alde puts such a job at probably over £5,000.
Q: Can Alde provide diesel heating?
Yes - both the Compact 4000 D and the 4000 D Plus run on diesel. The Compact 3030 and 3030 Plus can't heat on diesel themselves, but an Alde-equipped motorhome can have the engine heat exchanger fitted to use the engine's waste heat.
Q: Can underfloor heating alone heat my vehicle?
No. Even caravans and motorhomes built to the top BS EN 1645 grade aren't insulated like a house, so underfloor heating would have to run too hot to walk on to warm the whole vehicle by itself.
Q: Is the central heating under pressure like a car's cooling system?
No - it's an open-vented system, which keeps the weight down and reduces the draw on the leisure battery.
Q: Can the electric heating run from the leisure battery alone?
No. The controls run on 12V DC, but the electric heating elements need 230V AC mains. Away from hook-up, you'll need to heat with gas or diesel. Run from a leisure battery, the electric heating would produce only around 9 W - roughly a tenth of the heat your own body gives off.
Q: Is Alde heating heavier than blown-air heating?
When filled, it's about 10 kg heavier than a combi heater. Separate space and water heaters are generally less powerful these days, so they aren't a like-for-like comparison.
Q: Can copper parts be used in an Alde heating circuit?
No. Alde Compact boilers have aluminium surfaces inside the glycol cylinder, and any copper particles circulating into it would set up galvanic corrosion.